Fire Resistant Batt

Fire Rated Ablative Coated Mineral Batt - CE Marked (Single Pack 60mm)

Fire Resistant Board (Batt - Single Pack 60mm) | Shop At Stormflame

Fire Rated Ablative Coated Mineral Batt - CE Marked (Single Pack 60mm)

£25.14 £20.95 (ex. VAT)
Astro Batt Fire Resistant Board for sealing service penetrations | CE Marked | Tested to EN 1366-3 : 2009 and BS 476 Part 20 : 1987 | Certifire Approval.

Quantity:

Key Points:

  • Astro Batt.
  • Fire Resistant Board for sealing service penetrations in walls or floors.
  • Fire Resistant testing to EN 1366-3 : 2009 and BS 476 Part 20 : 1987.
  • Fire Classification to EN 13501-2.
  • Air Permeability testing to EN 1026 to 600Pa.
  • Acoustic Isolation testing to EN 10140 to 48dB.
  • Life expectancy of over 25 years.
  • Suitable for indoor use without additional environmental protection.

Description:
Fire Batt /Board consists of a stone fibre core coated on both sides with an ablative coating that transforms during a fire to prevent the passage of fire and smoke and the transfer of heat. Fire Resistant Board for sealing service penetrations in walls or floors. 50mm or 60mm thickness batt gives 4 hours fire and smoke barrier and up to 2 hours insulation.
Specification:

  • Batt : 600mm x 1200mm x 60mm: 140kgm³ density. (Single Pack)
  • COATING: 5kg Tub
Certification/Fire Test Reports:
  • Fire Resistant testing to EN 1366-3 : 2009 and BS 476 Part 20 : 1987.
  • Fire Classification to EN 13501-2.

Installation:

We have technical representatives who provide assistance in the selection and specification of the products on this site and should be consulted for exact installation and product suitability. Ensure an early engagement with ourselves, designers, main contractor and specialist installers before any installation. Other trades and/or manufacturers may need to be consulted. For in-depth information, specification and technical advice please call our Head Office on Tel: +(0)1329 841416 or email sales@stormflame.com

Maintenance:

All interested parties, designer, specifier, main contractor and specialist installers should provide access to allow the fire stopping seals to be regularly inspected and maintained, as well as records kept of such maintenance at minimum periods of 12 months, as required by the Regulatory Reform Order, and repaired if necessary. Reference should be made to ASFP TGD 17 – Code of Practice for the Installation and Inspection of Fire Stopping.

Competency:

It is vital that those entrusted to design or install a fire stopping product have the necessary levels of competence to undertake the task professionally and thoroughly. The level of competency required will be commensurate with the expected complexity of the building. All designers must eliminate, reduce or control foreseeable risks that may arise during installation, construction or maintenance when preparing or modifying designs. Clients should ensure that the principal designer and principal contractor carry out their duties under CDM regulations. The ASFP foundation course in passive fire protection provides essential knowledge as part of demonstrating competency and understanding in this key fire protection specialism.

Download and review any of the following information:

Certification/Fire Test Reports:

CE InformationCE Marked Documents
'DoP's are 'Declaration of Performance'
'CoC's are 'Certificate of Constancy of Performance'
'TDS's' are 'Technical Data Sheet'
'ETA's' are 'European Technical Assessment Sheet'

ul-eu_certification'UL Documentation' are 'UL - EU Certificate'
 

Don't forget to order your:
Batt Coating - Spray Grade
Pipe Collars
Pipe Wraps

or click "x" to close this box.

×
  • Product Code:
    AFB1200DC
  • MPN:
    AFB1200DC
Not yet reviewed
Write an online review and share your thoughts with other shoppers!
Be the first to review this product