Key Points:
- CE Marked.
- ULEU Accreditation.
- Fire resistance tested in flexible walls, rigid walls and floors.
- Tested in Linear Joints up to 50mm wide.
- Tested in large service openings up to 490 x 150mm.
- Tested with Metallic Pipes, Cables, Cable Bunches, Cable Trays and Cable Ladders, please refer to the test certification.
- For use in low movement joints, remains flexible.
- Shelf Life 18 months.
- Tested in accordance with EN1366-3:2009 - Fire Resistance - Penetration Seals.
- Tested in accordance with EN1366-4:2009 - Fire Resistance - Linear Seals.
- Classified in accordance with EN13501-2 - Fire Resistance.
- Tested in accordance with EN10140-2:2010 - Airborne Sound.
- Tested in accordance with EN1026:2000 - Air Permeability.
Description:
Astro Intu Mastic is a water based acrylic sealant used to reinstate the fire resistance of wall and floor constructions in linear joints and where apertures are penetrated by multiple services. Astro Intu Mastic Fire Resistant Sealant has been developed utilising specialist polymer technologies allowing it to be tested and Certified to internationally recognised standards, including CE marking and UL Listings. Astro Intu Mastic Fire Resistant has been tested and Certified as part the Fire Stopping range. The Astro Intu Mastic system can be installed across a variety services and substrates including,
- Flexible and Rigid Walls
- Rigid Floors
- Multi-Service penetrations
- Blank Openings
- Head of Walls
- Fire Batt
*For specific details please refer to the test certification.
Properties:
General Characteristics |
Inspection Method |
Value |
Product Data (uncured) |
Density (S.G) |
ASTM D792:13 |
1.63 |
Appearance |
|
Paste, matt finish |
Resistance to flow |
ISO 7390 : 2003 |
Pass |
Product Data (after curing) |
Hardness Shore A |
ISO 7619-1 : 2010 |
63/39 |
Movement Capability |
|
7.5% |
Operating Temperature °C |
|
-5 to 40 |
Loss Mass of Mass on Heating |
ISO 3451-1 (Method A) |
68.34 |
Flexibility - Bend Test |
ISO 1519 |
Pass |
Conditioning |
EOTA TR024 |
Type X |
Specification:
- Mastic is supplied in a discount pack of 12 cartridges (310ml).
- In an Off-White colour.
Installation:
We have technical representatives who provide assistance in the selection and specification of the products on this site and should be consulted for exact installation and product suitability. Ensure an early engagement with ourselves, designers, main contractor and specialist installers before any installation. Other trades and/or manufacturers may need to be consulted. For in-depth information, specification and technical advice please call our Head Office on Tel: +(0)1329 841416 or email sales@stormflame.com
Maintenance:
All interested parties, designer, specifier, main contractor and specialist installers should provide access to allow the fire stopping seals to be regularly inspected and maintained, as well as records kept of such maintenance at minimum periods of 12 months, as required by the Regulatory Reform Order, and repaired if necessary. Reference should be made to ASFP TGD 17 Code of Practice for the Installation and Inspection of Fire Stopping.
Competency:
It is vital that those entrusted to design or install a fire stopping product have the necessary levels of competence to undertake the task professionally and thoroughly. The level of competency required will be commensurate with the expected complexity of the building. All designers must eliminate, reduce or control foreseeable risks that may arise during installation, construction or maintenance when preparing or modifying designs. Clients should ensure that the principal designer and principal contractor carry out their duties under CDM regulations. The ASFP foundation course in passive fire protection provides essential knowledge as part of demonstrating competency and understanding in this key fire protection specialism.
Additional Notes:
Please refer to the ETA/UL-EU sheet for fields of application for this product. For further information on installation requirements please refer to the manufacturer of the services and the wall/floor specification to ensure the compatibility of this product, if in doubt please contact the technical team with services and wall/floor specification on Tel: +(0)1329 841416 or email sales@stormflame.com
Download and review any of the following information:
Certification/Fire Test Reports:
CE Marked Documents
'DoP's are 'Declaration of Performance'
'CoC's are 'Certificate of Constancy of Performance'
'TDS' are 'Technical Data Sheet'
'ETA's' are 'European Technical Assessment Sheet'
'UL Documentation' are 'UL - EU Certificate'
No reviews have been left for this product, be the first to